说明:双击或选中下面任意单词,将显示该词的音标、读音、翻译等;选中中文或多个词,将显示翻译。
您的位置:首页 -> 词典 -> 单芯电力电缆
1)  single-cored power cable
单芯电力电缆
1.
On the grounding mode for the metal sheathing of 35 ~ 110kV single-cored power cable;
35~110kV单芯电力电缆金属护层接地方式的探讨
2)  single core cable
单芯电缆
1.
The structure and main functions of single core cable were presented.
阐述了单芯电缆的结构及各部分的主要作用,分析了护层接地的原理,介绍了此接地方式在邯钢电缆线路上的实际运行。
3)  single cable
单芯电缆
1.
High speed down-hole transmission technology of video data with a single cable is introduced in this article.
文章介绍了单芯电缆高速传输井下视频数据技术的电路实现。
2.
The technology principle and circuit realization are introduced for pulse signal transmission through single cable.
介绍了用单芯电缆传输脉冲信号的技术原理和电路实现 ,分析了实现电路的耐压性能和传输性能。
4)  single conductor cable
单芯电缆
1.
According to the high current in the overhead contact line system (OCS) in the high speed railway lines, the induced voltage in metallic sheath of the single conductor cable was calculated with the effect of electric loops along the electrified railways taken into consideration.
高速铁路建设中,接触网系统出所馈线采用单芯电缆。
2.
A transmission scheme using single conductor cable in a Carbon/Oxygen logging tool is developed to meet the requirement of replacing conversional 7-conductor cable by single conductor cable.
针对测井电缆由7芯改为单芯的需要,提出了一种碳氧比测井仪单芯电缆传输方案。
5)  single-core cable
单芯电缆
1.
Consequently,the thermal time constant of single-core cable was introduced,transient thermal circuit models of cable body and its ambient medium were established,and the simplified equivalent ones were given.
为此,以单芯电缆为研究对象,介绍了电缆热时间常数;建立了电缆本体及周围介质的暂态热路模型并进行简化等效;计算了空气敷设和直埋敷设单芯电缆的热时间常数;并在试验现场进行了阶跃电流下的单芯电缆温升试验,通过对实测导体温度暂态过程的曲线拟合求得了电缆实际的热时间常数,验证了理论计算的正确性。
2.
Ampacity tests of the single-core cable are done in State Grid Electric Power Research Institute to conpare the detected cable temperature with the calculated, showing that they are basically in coincidence.
建立了基于IEC 60287电缆载流量计算的迭代算法;用此算法计算典型电缆线路的载流量与IEC算法的结果比较,两者相近,但迭代算法的精确度和适用范围都比IEC算法要好,理论上验证了迭代算法的正确性;在国网电科院进行单芯电缆载流量试验,将电缆各层温度和层间温差的实测值与迭代计算值比较,发现两者基本吻合。
3.
Recurrence formulas of transient temperature rise of its conductor only considering current change and only considering jacket temperature change are both derived to obtain the integrated superposition formula of calculating transient temperature of single-core cables.
为此,在电缆外皮温度监测的基础上,建立了单芯电缆暂态热路的数学模型;分别推导出只考虑电流变化和只考虑表皮温度变化两种情况下的暂态温升递推公式,进而推导出单芯电缆暂态温度的完整叠加公式;并采用经典4阶Runge-Kutta法求解微分方程组计算电缆本体温度。
6)  cross-linked power cable with single core
单芯交联电力电缆
1.
Based on the causes analysis of burning accidents of indoor terminal of 35 kV cross-linked power cable with single core and repairing procedures,the improvement methods and lessons to be drawn were raised.
通过对一起35kV单芯交联电力电缆户内终端烧毁事故进行原因分析,介绍了修复过程,并提出改进办法和应吸取的经验教训。
补充资料:110~500kV电力电缆


110~500kV电力电缆
110~500kV power cable

1 10~500 kVd旧、、}1 dlon{on110~500 kV电力电缆(110~500 kVpowereable)1 10一500 kV电力电缆为外包110~500kV级绝缘、并包有金属外皮的绞导线。按其绝缘介质分为自容式充油(简称OF)电力电缆和挤包绝缘电力电缆两大类。挤包绝缘电力电缆的绝缘介质主要为聚乙烯塑料,有交联聚乙烯(简称XLPE)和低密度聚乙烯(简称LDPE)两种。目前,水电站主要采用110~500 kV单芯高压电力电缆,用于主变压器高压侧的电力输出受地质、地形条件和枢纽布置的限制而采用架空线路技术经济又极不合理的场合。 不同绝缘介质电力电缆的主要优缺点如下: OF电力电缆开发较早,已取得较长期和成熟的制造、安装、维修运行经验;但需要设置一套供油装置,布置上略微复杂;当敷设高差较大时,由于其下终端油压较大易发生渗漏油现象,降低了可靠性,当高差超过Zoom时OF电力电缆的制造难度和价格将大为增加;OF电力电缆的介电常数、介质损失角tg占和损耗均远高于挤包绝缘电缆;因重量和尺寸较大、护套的机械强度较差、允许弯曲半径大,故运输、储存、现场安装、运行维护等均较为复杂和困难;特别是对防火要求严格,需相应设置一套消防设施,高差小时采用埋沙还较为简便,若对高差较大的地下厂房斜井或竖井布置则较为复杂、代价较大。 XLPE和LDPE两种挤包绝缘电缆相对OF电力电缆有共同的特点:如重量轻、允许弯曲半径仅为OF电缆的3/5左右;安装和布置简便,预制应力锥型电缆终端制作容易,施工工期短;故障修复时间较短;基本无需维护和监测;适应较大的敷设高差;绝缘性能均较好;介电常数和介质损失角tga较低;因自身具有难燃(或阻燃)特性故消防设施较为简单;近年来其价格已迅速降到可比OF电力电缆更低的趋势等。 但这两种挤包绝缘电缆也各有优缺点和特色:XLPE电力电缆电流载荷、抵抗热变形特性和机械特性比LDPE电力电缆好些,故前者电缆的允许温度较高,在同一额定电流下其导体截面一般比后者要小些。XI子PE电缆绝缘介质的交联工艺复杂,制造过程中对介质纯度控制的难度较大、要求较为严格,否则将对其绝缘性能带来较大影响。而LDPE电缆绝缘介质的提纯工艺较简单、易控制,增加特殊添加剂后大大改善了绝缘性能(由42 kV/rnm提高到65 kV/mm);la]时,LDPE电缆介质纯度较高,杂质含量较少、水分含量较低,故其介质损失角tg占和介质损耗均比XLPE电缆低。 500 kV OF电力电缆的生产始于20世纪70年代初。日本住友(Sumitomo)公司1973年为日本()kutataragl抽水蓄能电站安装第一回500 kV()F电力电缆(高差约90m),1977年向美国大古力水电站出口500 kV OF电力电缆(高差约20Om)。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。
参考词条